Fire Detectors
In two words. Linear smoke detectors IPDL cover zones up to 150 m using an optical "emitter–reflector" channel, while multi-channel flame detectors of the "Tyulpan" series detect electromagnetic radiation of flames in one or several spectral bands (IR, UV). Both lines operate at 8–28 V, feature protection up to IP68, and are designed for industrial facilities: warehouses, gas stations, oil storage, tunnels, and parking garages.
Fire Detectors — 2 lines in one section
Linear smoke IPDL and flame "Tyulpan" · models, differences and recommendations for useLinear Smoke Detectors IPDL
Linear principle: the emitter sends an optical signal to a reflector, and the receiver detects signal attenuation caused by smoke between them. A single unit covers up to 150 m without intermediate nodes.
| Model | Type | Range, m | Features |
|---|---|---|---|
| IPDL-S-I | Single-component (emitter+receiver in one housing) | 4–150 | Base model, Bluetooth |
| IPDL-S-I v.5 | Single-component | 4–150 | Arctic (−40 °C), optics heater |
| IPDL-D-I | Two-component (emitter + receiver) | 4–150 | Separate installation |
| IPDL-D-I v.5 | Two-component | 4–150 | Arctic, heater |
| IPDL-S-II | Single-component, 2nd gen | 4–150 | Improved dust compensation |
| IPDL-S-II v.5 | Single-component | 4–150 | Arctic, heater |
| IPDL-D-II | Two-component, 2nd gen | 4–150 | Improved compensation |
| IPDL-D-II v.5 | Two-component | 4–150 | Arctic, heater |
| IPDL-D-I/4p | Single-position, 4 directions | up to 150 | Wide angle, single position |
| IPDL-D-II/4p | Dual-position, 4 directions | up to 150 | Two independent barriers |
| IPDL-D-II/4p v.5 | Dual-position, IP65, heater | up to 150 | Arctic, outdoor |
Common specifications (per IPDL-S-I operation manual):
- Supply voltage: 8–28 V
- Current consumption (external supply): standby ≤ 4 mA; "Fire" mode 7.5 mA; "Fault" mode 0.7 mA
- Loop-powered: standby ≤ 0.7 mA
- Heater unit current (v.5): ≤ 250 mA
- Range: 4–150 m depending on the number of reflectors — 1 → up to 50 m; 2 → up to 75 m; 4 → up to 100 m; 8 → up to 150 m
- Operating temperature: −25…+55 °C (standard), down to −40 °C (v.5, optics heater)
- Protection: IP41 (standard), IP65 (v.5)
- Automatic optics dust compensation
- Adjustable detection threshold
- Last-event memory
- Remote monitoring via VUOS
- Service life: 10 years
IPDL Accessories
| Item | Purpose |
|---|---|
| Reflector for IPDL | Optical reflector (kit with detector) |
| Heater module MP-1 / MP-2 | Optics heating in cold weather |
| Filter FP-1 | Calibration and testing |
| Attenuator FOS-1 | Signal attenuation for threshold setup |
| Clamp SC-11 / SC-21 | Pipe / I-beam mounting |
| Rail RK-301 / RK-601 / RK-801 | Height-adjustable mounting |
| Bracket KDT-2611 / 4020 / 8020 | For I-beams |
| Rotating bracket KP-3467 / KPI-1 / KPI-2 | Precise alignment |
| Protective cover KZh-1 / KZh-2 / KZh-11 / KZh-21 | Weather and mechanical protection |
| Commutation block MK-2760, BK-2727/2728 | Loop connection |
| Control unit PK-02 | Setup and diagnostics |
| Laser pointer LU-151 | Optical axis alignment |
Flame Detectors "Tyulpan"
Detect electromagnetic radiation of flames. Numbering: first digit — number of spectral channels, second — modification.
| Model | Spectrum | Protection | Application |
|---|---|---|---|
| Tyulpan 1-1 | 1×IR | IP65 | Base open-flame detection |
| Tyulpan 2-14 | 3×IR | IP66/IP68 | High reliability, wet environments |
| Tyulpan 2-16 | IR+UV | IP66/IP68 | Maximum interference rejection |
| Tyulpan 2-18 | UV | IP66/IP68 | Fast response, gas fires |
| Tyulpan 3-1 | 2×IR | IP65 | Dual-channel monitoring |
| Tyulpan 3-14 | 3×IR | IP65 | Triple-channel monitoring |
| Tyulpan 3-16 | IR+UV | IP65 | Combined |
| Tyulpan 3-18 | UV | IP65 | UV detection |
Explosion-proof (Ex)
For hazardous areas (gas stations, oil storage, chemical plants):
| Model | Spectrum | Ex zone |
|---|---|---|
| Tyulpan 2-14 Ex | 3×IR | IIA, IIB |
| Tyulpan 2-16 Ex | IR+UV | IIA, IIB |
| Tyulpan 2-18 Ex | UV | IIA, IIB |
| Tyulpan 4 Ex | Combined | IIA, IIB |
Specialized variants
| Model | Purpose |
|---|---|
| Tyulpan 1-1-1 | Monitor nozzles, fire trucks |
| Tyulpan 2-16-3-2 | Monitor nozzles (IR+UV) |
| Tyulpan 2-16-3-2 Ex | Monitor nozzles, explosion-proof |
| Tyulpan 1-1-0-1 | Coal conveyors |
Common specifications:
- Supply voltage: 8–28 V
- Operating temperature: −40…+70 °C (standard, Tyulpan 1-1), −60…+50 °C (Ex)
- Output: dry contact (relay)
- Response time: < 1 s (UV), ≤ 15/16 s (IR, Tyulpan 1-1)
- Fire safety certificate
Documentation
| Series | PS / RE |
|---|---|
| IPDL-S-I | RE |
| Tyulpan 1-1 | PS / RE |
| Tyulpan 2-16 | PS |